Description

Relay protection tester

1. Ac current source (3*30A) Single-phase current output (RMS) 0-30A/phase, accuracy: 0.2% ±5mA

 

Three-phase parallel output (RMS) 0-90A/three parallel outputs of the same phase

 

Phase current long-term allowable working value (effective value) 10A

 

Maximum output power 300VA per phase

 

The maximum output power of three-phase parallel current is 800VA

 

The maximum allowable working time of the current output is 5s

 

Frequency range 0–1000Hz, accuracy 0.001Hz

 

Harmonic frequency 2-20 times

 

Phase 0–360°, accuracy 0.1°

2. Dc current source Dc current output 0–±10A/ phase, accuracy: 0.5% ±5mA
3. Ac voltage source Single-phase voltage output (RMS) 0-120V/phase, accuracy: 0.2% ±5mV

 

Line voltage output (RMS) 0-250V

 

Phase voltage/line voltage output power 75VA/100VA

 

Frequency range 0-1000Hz, accuracy: 0.001Hz

 

Harmonic frequency 2-20 times

 

Phase 0–360°, accuracy: 0.1°

4. Dc voltage source Single-phase voltage output amplitude 0–±150V, accuracy: 0.2% ±5mV

 

Line voltage output amplitude 0–±300V

 

Phase voltage/Line voltage Output power 90VA/180VA

5. Switching terminal Switch input terminal 8 pairs

 

Air contact 1–20mA, 24V device internal active output

 

Potential flip passive contact: low resistance short-circuit signal

 

Active contact: 0-250V DC

 

4 pairs of switching output terminals, empty contact, breaking capacity: 110V/2A, 220V/1A

6. other Time range 1ms–9999s, measurement accuracy: 1ms

 

Unit volume weight Volume 328 x 168 x 250mm3, about 12.5Kg

 

Power supply AC220V±10%, 50Hz, 10A

7. Ac current operating time 10A≥ Working current Working time > 60 minutes

 

20A≥ Working current ≥10A Working time > 70S

 

30A≥ Working current ≥20A Working time > 15S

 

Working current ≥30A Working time > 5S

 

Relay protection tester