Descriere

TAG-8600 Nuclear Phase Tester

Introducerea Produsului
TAG-8600 wireless high voltage nuclear phase meter is used for phase verification and phase sequence verification of high voltage power lines and substations. It adopts the latest power electronic testing technology and wireless transmission technology, safe and reliable operation, ușor de folosit, overcome many shortcomings of wired nuclear phase device, in line with the national power safety equipment quality supervision and inspection.

 

TAG-8600 Nuclear Phase Tester

Caracteristicile produsului
1, can measure high and low voltage wireless speech nuclear phase, frecvenţă, phase, phase sequence, electrical testing.
2, display mode: 3.5 inch true color LCD display

 

TAG-8600 Nuclear Phase Tester

Parametrii produsului

Work and energy High and low voltage wireless speech nuclear phase, frecvenţă, phase, phase sequence, electrical testing
Sursa electrica DC 3.7V rechargeable lithium battery, USB charging interface, continuous working for about 10 ore
transmission mode 315MHz、433MHz wireless transmission
Nuclear phase distance About 160m Max
display mode 3.5 “true color LCD display
Gamă Nuclear phase voltage level: AC 10V ~ 550kV
phase position:0.0°~360.0°
frecvenţă:45Hz~75Hz
rezoluţie 0.1°;0.1Hz
Precizie (23℃±5℃, below 80%RH) phase position:≤±10°
phase position:≤±2Hz
Phase differentiation In-phase :-30° ~ 30°; Out of phase: 90° ~ 150° and 210° ~ 270°
phonetic function In-phase, out-of-phase, X signal normal, Y signal normal and other voice functions
Insulation rod size After stretching, the length is about 3.2m. Aproximativ. 0.6m after shrinkage (opțional 5 m rod)
stocare a datelor 9999 group
Nuclear phase mode Contact nuclear phase: the bare wire below 35kV, or the wire with safety insulation skin below 110kV directly contact the nuclear phase. (with insulated rod operation)
Non-contact nuclear phase: bare wires above 35kV, or lines above 110kV using non-contact nuclear phase, gradually close to the wire. (with insulated rod operation)
Charge indicator The detector beeps “du-du-du-duk”
shift automatic gear change
sample rate 2 times per second
meter size Detector: Lungime, width and thickness 145mm×60mm×48mm
Receptor: Lungime, width and thickness 250mm×100mm×40mm
Backlight control Press the up and down arrow keys to adjust the backlight brightness
Induction intensity control According to the induced electric field strength, the detector can automatically control the magnification, which is convenient for the nuclear phase where the line is dense
data-hold In test mode, press the HOLD key to HOLD data, and then press the Hold key to cancel the hold
Exit Function Press ESC to exit the current function screen and return to the upper-level directory
World Data Referral Centre Press ENTER to enter the data view mode, press the arrow key to browse the saved data
No-signal indication The “—-” symbol is displayed dynamically when the receiver does not receive the transmission signal
automatic shut After about 15 minutes of power on, the meter automatically shuts down to reduce battery consumption
automatic shut When the battery voltage is below 3.2V:
Detector: The power indicator blinks slowly, reminding to charge;
Receiving end: The battery low voltage symbol is displayed, reminding to charge
rated current Detector: 35mA max; Receptor: 300mA max
Instrument quality Detector: 205g(including battery)
Receptor: 395g(battery included)
Insulation rod: 1.2kg (3m rod), 1.45kg(5m rod)
Total mass: 7kg(including instrument box, equipped with 5 meter rod and box about 9.8kg)
Operating temperature and humidity Operating temperature and humidity
Storage temperature and humidity -10℃ ~ 60℃; Below 70%Rh
Dry disturbance No extra-strong electromagnetic field; No 433MHz, 315MHz same frequency interference
dielectric strength Insulation rod: AC 110kV/rms(after the insulation rod is fully stretched, between the two ends)
Detector: 2000V/rms(between the two ends of the housing)
Receptor: 2000V/rms(between the two ends of the housing)
structure Drip proof Type II, IP63
Fit for safety

 

GB13398-92、GB311.1-311.6-8、3DL408-91Standard and the new national power industry standard “1kV ~ 35kV portable nuclear phase device general technical conditions DL/T971-2005” requirements
Comply with IEC61481-A2:2004; IEC 61243-1 ed.2:2003 standard