KGSB-23 live cable identification instrument

Product Introduction
KGSB-23 Live cable identification instrument is designed for power cable engineers and cable workers to solve the technical problems of cable identification. The user can accurately identify one of the target cables from multiple cables through the instrument to avoid serious accidents caused by missawing live cables.
KGSB-23 live cable identification instrument has the functions of live cable identification, power failure cable identification, AC current test, AC voltage test, and is composed of transmitter, transmitting current clamp, receiver, receiving flexible current clamp, etc.

 

KGSB-23 live cable identification instrument

Product Characteristics
1. The user accurately identifies one of the target cables from multiple cables through the instrument to avoid serious accidents caused by missawing live cables.
2, cable identification is from the operation of both ends of the cable, we must ensure that the double number of the cable is accurate, the instrument design uses PSK technology, combined with accurate algorithms. No matter how reliable the memory of field workers is, it is no substitute for the recognition of professional instruments.
3, at the same time with live cable identification, power failure cable identification, AC current test, AC voltage test function, by the transmitter, transmitting current clamp, receiver, receiving flexible current clamp and so on.

 

KGSB-23 live cable identification instrument

Product Parameters

Transmitter technical parameters

Function The composite pulse frequency current signal is emitted, the remaining battery voltage is displayed, and the emission state is dynamically indicated
Electric source The composite pulse frequency current signal is emitted, the remaining battery voltage is displayed, and the emission state is dynamically indicated
output mode Caliper coupling during electrification identification; Power outage identification directly connected output
emission frequency 625Hz, 1562Hz, 2500Hz, 10KHz (live identification), press the up and down arrow key to adjust the transmission frequency
impulse voltage 500V (when power failure is recognized)
pulse current Max 5A (depending on the size of the loop resistance)
impulse frequency 1 time/second
pulse width 2ms
Inside diameter of firing clamp φ120mm
Test line length 1 time/second
Firing clamp size Length and breadth 300mm×175mm×50mm
Inside diameter of firing clamp φ120mm
Launching clamp wire length 2m
Ground pin size Length and breadth 225mm×100mm×10mm
Transmitter size 320mm×275mm×145mm
Firing clamp size Length and breadth 300mm×175mm×50mm
display mode Large LCD displays the remaining battery voltage in real time with backlight
LCD size Length and width 128mm×75mm; The display domain is 124mm x 67mm
out packing size length, width and height 400mm×245mm×335mm
operating temperature -10℃~40℃
storage condition -20℃~50℃,≤95%RH, non condensing
Backlight control Yes, white backlight
operating temperature -10℃~40℃
storage condition -20℃~50℃,≤95%RH, non condensing
Instrument quality Transmitter 2.5kg; Launching clamp 1.08kg; Total weight 4.4kg (including receiver)
battery capacity When the battery voltage is lower than 9.65V, the battery low voltage icon is displayed to remind you to charge the battery. When it is lower than 9.5V, the device automatically shuts down
charger 12.6V DC charger
charging port Circular charging interface, DC logo
Compression resistance The transmitter adopts the integrated special tool box design, the box can withstand the pressure of about 200kg
Pressure resistance AC 3700V/rms(Instrument box top and bottom before)
electromagnetic property IEC61326(EMC)
Reference safety IEC61010-1(CAT Ⅲ 300V、CAT IV 150V、Pollution Level 2)