Description

Generator insulation megger

Main feature
1, using 32-bit microcontroller control, Chinese operation interface, easy to operate.
2, large output current, (2500V output greater than 25mA), short circuit current ≧25mA.
3, high voltage generation module adopts closed technology, internal protection resistance, safe and reliable.
4, strong anti-interference ability, can meet the field operation of ultra-high voltage substation.
5, automatic discharge after the test, and real-time monitoring of the discharge process.
6, suitable for measuring the insulation resistance, absorption ratio (R60S/R15S) and polarization index (R10min/R1min) of the water-cooled generator.
7, test high voltage 2500V/5000V.
8, automatic compensation and adjustment of water polarization potential. The resistance between the frame and the sink pipe is as small as 10kΩ to ensure measurement accuracy
9, the output power is large, the load resistance between the line and the sink pipe can be as low as 100kΩ(2500V)/150kΩ (5000V) insulation resistance measurement can be as low as 1MΩ(2500V)/2MΩ(5000V).
10, the insulation resistance value is indicated by the analog progress bar, which can visually observe the test process of the capacitive test without delay. Logarithmic scale, indicating the value of small jump, easy reading.
11, digital display using 3 1/2 LCD digital table.
12, LCD timer displays the test time, and shows its minutes and seconds in a cycle of 0 ~ 32 minutes. It buzzes every 15 seconds.
13. It can automatically measure and remember R15S, R60S, R10min, absorption ratio and polarization index for review and reading when the test is completed.
14, with automatic compensation and adjustment of water polarization potential.

Generator insulation megger

 accuracy ±(5%+5 words); Measuring range: 0.1M ~ 200GΩ
display mode digital and analog progress bar dual display. Temperature measurement: -25℃ ~ 125℃
 test voltage range  2.5KV, 5.0KV
 short circuit current ≧25mA Measurement time: 1 minute ~ 10 minutes (related to the measurement method)
 charging power supply  180 ~ 270VAC,50Hz/60Hz±1% (mains or generator power supply)
 working environment  temperature -10 ~ 40℃, relative humidity 20 ~ 80%

Generator insulation megger Generator insulation megger Generator insulation megger