TAG-8600 wireless high voltage nuclear phase meter is used for phase verification and phase sequence verification of high voltage power lines and substations. It adopts the latest power electronic testing technology and wireless transmission technology, safe and reliable operation, facile da usare, overcome many shortcomings of wired nuclear phase device, in line with the national power safety equipment quality supervision and inspection.

 

TAG-8600 Nuclear Phase Tester

Caratteristiche del prodotto
1, can measure high and low voltage wireless speech nuclear phase, frequenza, phase, phase sequence, electrical testing.
2, modalità display: 3.5 inch true color LCD display

 

TAG-8600 Nuclear Phase Tester

Parametri del prodotto

Work and energy High and low voltage wireless speech nuclear phase, frequenza, phase, phase sequence, electrical testing
Electric source DC 3.7V rechargeable lithium battery, USB charging interface, continuous working for about 10 ore
transmission mode 315MHz、433MHz wireless transmission
Nuclear phase distance About 160m Max
modalità display 3.5 “true color LCD display
Allineare Nuclear phase voltage level: AC 10V ~ 550kV
phase position:0.0°~360.0°
frequenza:45Hz~75Hz
risoluzione 0.1°;0.1Hz
Precisione (23℃±5℃, below 80%RH) phase position:≤±10°
phase position:≤±2Hz
Phase differentiation In-phase :-30° ~ 30°; Out of phase: 90° ~ 150° and 210° ~ 270°
phonetic function In-phase, out-of-phase, X signal normal, Y signal normal and other voice functions
Insulation rod size After stretching, the length is about 3.2m. Approx. 0.6m after shrinkage (opzionale 5 m rod)
data storage 9999 group
Nuclear phase mode Contact nuclear phase: the bare wire below 35kV, or the wire with safety insulation skin below 110kV directly contact the nuclear phase. (with insulated rod operation)
Non-contact nuclear phase: bare wires above 35kV, or lines above 110kV using non-contact nuclear phase, gradually close to the wire. (with insulated rod operation)
Charge indicator The detector beeps “du-du-du-duk”
shift automatic gear change
sample rate 2 volte al secondo
meter size Rivelatore: Lunghezza, width and thickness 145mm×60mm×48mm
Receiver: Lunghezza, width and thickness 250mm×100mm×40mm
Backlight control Press the up and down arrow keys to adjust the backlight brightness
Induction intensity control According to the induced electric field strength, the detector can automatically control the magnification, which is convenient for the nuclear phase where the line is dense
data-hold In test mode, press the HOLD key to HOLD data, and then press the Hold key to cancel the hold
Exit Function Press ESC to exit the current function screen and return to the upper-level directory
World Data Referral Centre Press ENTER to enter the data view mode, press the arrow key to browse the saved data
No-signal indication IL “—-” symbol is displayed dynamically when the receiver does not receive the transmission signal
automatic shut After about 15 minutes of power on, the meter automatically shuts down to reduce battery consumption
automatic shut When the battery voltage is below 3.2V:
Rivelatore: The power indicator blinks slowly, reminding to charge;
Receiving end: The battery low voltage symbol is displayed, reminding to charge
corrente nominale Rivelatore: 35mA max; Receiver: 300mA max
Instrument quality Rivelatore: 205G(including battery)
Receiver: 395G(battery included)
Insulation rod: 1.2kg (3m rod), 1.45kg(5m rod)
Total mass: 7kg(including instrument box, equipped with 5 meter rod and box about 9.8kg)
Operating temperature and humidity Operating temperature and humidity
Storage temperature and humidity -10℃ ~ 60 ℃; Below 70%Rh
Dry disturbance No extra-strong electromagnetic field; No 433MHz, 315MHz same frequency interference
dielectric strength Insulation rod: AC 110kV/rms(after the insulation rod is fully stretched, between the two ends)
Rivelatore: 2000V/rms(between the two ends of the housing)
Receiver: 2000V/rms(between the two ends of the housing)
struttura Drip proof Type II, IP63
Fit for safety

 

GB13398-92、GB311.1-311.6-8、3DL408-91Standard and the new national power industry standard “1kV ~ 35kV portable nuclear phase device general technical conditions DL/T971-2005” requirements