Conversion Resonance Test Device
Subjects and test requirements
1. Ac voltage withstand test of 10kV/300mm², length 1.5km cable, capacitance ≤0.563uF, test frequency 30-300Hz, test voltage 22kV, test time 5min.
2, 35kV main transformer AC withstand voltage test, capacitance ≤0.02uF, test frequency 45-65Hz, test voltage does not exceed 68kV, test time 1min.
Ambiente di lavoro
1. Ambient temperature: -150C – 450C;
2. Relative humidity: ≤90%RH;
3. Altitude: ≤3000 meters;