KGJD-K SF6 Gas Density Relay Calibrator
- Paglalarawan
- Pagtatanong
Paglalarawan
KGJD-K SF6 Gas Density Relay Calibrator
Pagpapakilala sa Produkto
KGJD-K SF6 gas density relay calibrator is an intelligent SF6 gas density relay calibrator. Using embedded microprocessor, the calibrator can check the performance of various SF6 gas density relays, and perform standard conversion of SF6 gas pressure at any ambient temperature. It is mainly used for the production, maintenance and monitoring of SF6 gas products. It is especially suitable for power system, which provides convenience for production, safe operation, pre-test and maintenance of SF6 electrical products.
KGJD- KSF6 gas density relay calibrator absorbs the advanced experience of similar products in China, uses the advanced and accurate mathematical model of the relationship between RTSF6 gas pressure and temperature, and designs a RTSF6 gas density relay calibration equipment according to the needs of field testing. Using embedded microcomputer technology and imported high performance pressure and temperature sensors, the difficulty of calibration of RTSF6 gas density relay is solved. The calibrator simultaneously samples the gas pressure and temperature of the relay under test, and automatically converts it to the standard pressure value at 20℃, thus completing the dynamic automatic compensation of pressure and temperature. Kaya nga, the calibrator does not need the constant greenhouse used by the traditional experimental method, and avoids a large amount of SF6 gas waste.
In a sealed container, SF6 gas pressure at a certain temperature can represent SF6 gas density. In order to be unified, it is customary to take the pressure of SF6 gas at 20 ° C as the representative value of its corresponding density. Kaya nga, SF6 gas density relays use the pressure of SF6 gas at 20 ° C as a scale value. In the field calibration, the measured pressure at different ambient temperatures
KGJD-K SF6 Gas Density Relay Calibrator
Mga Parameter ng Produkto
1, nagtatrabaho supply ng kuryente: AC and DC dual purpose
2, katumpakan: 0.25 level
3, display mode: Chinese liquid crystal
4, printing method: pin type micro
5, measuring pressure range: 0 ~ 1.0Mpa
6, measuring temperature range: -20℃ ~ +70℃;
7, check pressure range: 20℃ standard pressure 0.1 ~ 0.9Mpa;
8, instrument weight: about 3.5Kg
9, the use of conditions: ambient na temperatura: -20℃ ~ 60℃ Relative humidity: not more than 93% (25°C)
10. Overall size: 360×260×130mm
KGJD-K SF6 Gas Density Relay Calibrator
Mga Katangian ng Produkto
KGJD- KSF6 gas density relay calibrator absorbs the advanced experience of similar products in China, uses the advanced and accurate mathematical model of the relationship between SF6 gas pressure and temperature, and designs a SF6 gas density relay calibration equipment according to the needs of field testing. By adopting embedded microcomputer technology and selecting imported high performance pressure and temperature sensors, the difficulty of calibration of SF6 gas density relay is solved. The calibrator simultaneously samples the gas pressure and temperature of the relay under test, and automatically converts it to the standard pressure value at 20℃, thus completing the dynamic automatic compensation of pressure and temperature. Kaya nga, the calibrator does not need the constant greenhouse used by the traditional experimental method, and avoids a large amount of SF6 gas waste. It has the following significant characteristics:
1, compact na istraktura, maliit na sukat, magaan ang timbang, madaling dalhin.
2. High degree of mechatronics, advanced technology and reliable performance.
3, malaking screen LCD, Chinese menu, intuitive and simple.
4, the power supply has UPS function, suitable for field operations.
5, equipped with a micro printer, print test results at any time.
6, good sealing performance, no waste of SF6 gas in the verification process.
7. Both ends of the connected gas pipe are equipped with an inlet quick check valve, which is easy to operate and prevents the pipeline from entering water and air. Most density relays can be verified directly without disassembly.
8, the sampling point is equipped with an intelligent voltage protector, the sampling point fish clamp mistakenly connected to 220V voltage will not damage the calibrator, the use of safer.
9, the temperature sensor is located in the instrument gas pipeline, correctly reflect the gas temperature in the density relay, more accurate measurement.
KGJD-K SF6 Gas Density Relay Calibrator
Mga tampok ng produkto:
1. The alarm action and pressure value of various SF6 gas density relays at any ambient temperature are measured, and automatically converted to the corresponding standard pressure value at 20℃ to realize the alarm performance verification of SF6 gas density relays
2. Measure the locking action and pressure value of various SF6 gas density relays at any ambient temperature, and automatically convert it to the corresponding standard pressure value at 20℃ to realize the locking performance verification of SF6 gas density relays.
3, if the calibrated SF6 gas density relay is attached with a pressure gauge or density meter, the calibrator can also verify the accuracy of the pressure gauge or density meter.
4, any ambient temperature SF6 gas pressure to 20℃ when the standard pressure conversion.
5, the standard pressure at 20℃ to any temperature pressure conversion.