Descripción

vector analyzer

The company according to the needs of field testing, timely development of KDZD566 multi-function vector analyzer.
KDZD566 multi-function vector analyzer integrates multiple functions and has a variety of measurement functions, el

main measurement functions are:
Phase meter function – check the correctness of main variable differential protection and busbar differential;
Electrical parameter tester function – test the parameters of the power system;
Metering wire detector function – to detect three-phase three-wire power metering wire inspection;
Harmonic content test function – field test of harmonic content of voltage and current;
Oscilloscope function – Display bar chart, as a simple oscilloscope, used to observe the test signal waveform.
The measuring instrument adopts dsp AC sampling, can measure 3 voltage and 6 current analog at the same time, the instrument 9 channel vector display on the same screen, human-machine dialogue interface is friendly; Independently developed hand-held mold structure, high strength engineering plastic, strong and light, fácil de usar, greatly convenient for field use, is the power worker’s right-hand assistant.

vector analyzer
Functional characteristics
1, three voltage, six current vector on the same screen display, for the differential protection device test only one connection can complete the drawing of the hexagonal diagram, greatly improve the work efficiency; In the case of small space and difficult wiring, the double-clamp method can be used for multiple measurements and finally draw a complete hexagonal diagram.
2, the use of clamp current transformer connection, no need to disconnect the current circuit, safe and convenient.
3, can carry out vector analysis of complex protection devices, judge whether the wiring is correct, and give the correct wiring diagram for comparison.
4, conventional electrical parameters can be tested, while displaying three-phase voltage, corriente trifásica, three-phase active power, three-phase apparent power, three-phase phase Angle; The voltage amplitude, current amplitude and power value of the primary side of the transformer can be directly read and converted.
5, can carry out three-phase three-wire high-voltage metering device error wiring check, can analyze and judge the three-phase three-wire 48 kinds of wiring, directly give the analysis results; Investigate and punish the means of stealing electricity by maliciously changing the metering connection to effectively avoid the loss of electricity charges.
6, can carry out harmonic analysis of the measured signal on the spot, can analyze the content of 2-21 Armónicos, and automatically calculate the total harmonic distortion degree.
7, large screen, high brightness color LCD display, Chinese graphic menu and operation prompts to achieve friendly human-machine dialogue, touch the silicone button to make the operation more comfortable, feel better, wide temperature LCD with brightness adjustment, can adapt to winter and summer seasons.
8, large capacity lithium battery power supply, continuous work up to 8 horas.
9, the user can real-time test data in the form of records saved for centralized management, filing, acceso, can store more than 200 groups of data.
10. The saved records can be uploaded to the background management computer for comprehensive analysis and review.
11, with perpetual calendar, clock function, real-time display of the date and time of the test work.
12, talla pequeña, peso ligero, fácil de usar en el sitio.
13, reserve USB interface, available instruments to replace flash disks and other mobile storage devices.

vector analyzer

1. Enter features
Number of voltage channels 3
Voltage measurement range 20~450V
Voltage display resolution 0.01V
Current channels 6 canales
Current measurement range 0~10A
Current display resolution 0.0001A
Rango de medición de fase -180° ~ +180°
Harmonic analysis times 2 ~ 21 veces
2. Exactitud
Voltaje ±0,2%
Actual, fuerza ±0,2%
Ángulo de fase ±1°
Measurement error of harmonic voltage content ≤ 0.3%
Measurement error of harmonic current content ≤ 0.5%
temperatura de trabajo -15℃~ +40℃
charging power supply AC 160V~260V
aislamiento ⑴, Voltaje, current input end of the insulation resistance to the housing ≥100MΩ.

(2) The working power input side is subjected to a power frequency of 2KV (valor efectivo) between the shell, which lasts 1 minute experiment.

volumen 250mm×160mm×60mm
Peso 1.8Kg

vector analyzer vector analyzer vector analyzer