cable grounding fault locator

KDJK-10 distribution network overhead line single-phase grounding fault locator is suitable for 6-35kV overhead line single-phase grounding fault line, when the line is shut down due to single-phase grounding fault, the equipment can be accurately located at the docking point.

KDJK-10 single-phase ground fault locator for overhead lines in distribution network is a set of portable equipment, which can locate faults of multiple lines. The whole equipment consists of KDJK-10 transmitter, KDJK-A sensor, KDJK-B receiver and accessories. After the fault line is shut down, the transmitter applies ultra-low frequency high voltage signal to the line to make the fault repeat, and the sensor is hung on the line with an insulated rod along the line to detect the signal, and the data is transmitted wirelessly to the receiver on the ground, and the receiver displays the measurement result. Before the fault point, the current continues to exist, after the fault point, the current disappears. The fault location can be quickly determined by rough segmentation followed by precise fixing.

cable grounding fault locator

Caracteristicas de producto
1. Suitable for distribution network of small current grounding system, detecting single-phase metallic grounding, arco, La conexión a tierra de la resistencia de transición y otras fallas de las líneas aéreas.
2. Locate the line after it stops running, especially for faulty lines with cable branches.
3. By injecting detection signals into the fault phase of the line to determine the single-phase grounding fault point, reduce blindness and shorten the fault detection time.
4. En el estado de la falla de energía de línea, the single-phase ground fault can be quickly and accurately located, and the error must not exceed 1 metro.
5. Using dichotomy for detection, without the need for full line inspection, shorten the fault detection time.
6. Cuando la línea se ejecuta normalmente, la corriente de carga de línea (0-1000A) se puede detectar.
7. Operate on the ground through the insulation rod, y debe haber un dispositivo de protección de fusibles dentro del dispositivo para garantizar la seguridad personal..
8. The device built-in ultra-low frequency composite signal source, fuente de señal de alimentación, high voltage signal source a variety of power modules, the device to achieve a variety of working modes.
9. El dispositivo está equipado con una variedad de sistemas receptores, que no interfieren entre sí, y se puede probar simultáneamente o por separado.
10. Apply a high voltage signal to make the fault repeat, the current signal is stable and easy to detect.
11. Ultra-low frequency signal avoids the influence of system distributed capacitance, and can locate faults with high resistance values.
12. Características de seguridad del transmisor: función de bloqueo de arranque de alto voltaje, La salida permite un cortocircuito directo.
13. The sensor uses high sensitivity sensor, open design, no need to close, easy to connect on the line.
14. Transmisión de comunicación inalámbrica de sensor y receptor, seguro y confiable.
15. The signal and data measured by the device may be saved to the system background, and the communication protocol is universal.
16. El dispositivo tiene una variedad de funciones de protección y tiene un buen rendimiento de la prueba de seguridad.
17. The transmitter can use mains power, generator power supply, sensor and receiver dry battery power supply.
18. When the power supply voltage is too low, the alarm should be prompted to charge.
19. The size of the different frequency signal sent is adjustable.
20. The frequency and power signal are adjustable.
21. Operate through the insulated rod and have a fuse protection device inside.
22. The device built-in ultra-low frequency composite signal source, fuente de señal de alimentación, high voltage signal source a variety of power modules, the device to achieve a variety of working modes.
23. Small size and light weight of transmitter; The sensor is designed to reduce the volume and weight, and it is convenient to connect along the line. The receiver is designed for handheld.
24. The receiver uses a large-screen LCD display to display the sensor status, current waveform and current value.

Test signal generator

Alcance de la aplicación 6-35kV overhead line single-phase ground fault line
Positioning accuracy 0.2metro.
Transmitter output characteristics
Frecuencia de salida 1Hz
Open circuit voltage fundamental wave RMS 0 ~ 2800V
Current test range 100mamá
Rango de medición de falla a tierra Resistencia al suelo ≤100 kΩ
Pulsating DC 0 ~ 8kV, equivalent to the peak phase voltage of 10kV lines
Longitud de la línea de detección ≥120 km
Short-circuit current fundamental wave RMS 0 ~ 30 mapa
Rango de salida de señal 0 ~ 100 mapa
Precisión de salida de señal ± 1MA
Wireless communication distance between sensor and receiver not less than 30m

Transmitter output power: Maximum power 900W

Transmitter power supply AC 220V mains, generador (output power ≥1500W)
Peso 15kg
Volumen 455×335×310mm

Signal transmitting sensor

Detect the cross-frequency signal emitted by the test signal generator.
Automatic timing
Automatically displays the communication status with the pliers meter.
Automatic display of device voltage.
Automatic low voltage alarm.
Detects the load current of the line.
Clamp CT was used to measure the different frequency signal and load current.
Can be used to measure insulated lines.
Can display the current clamp battery status and battery voltage in real time.
Precisión de la prueba ±1%±3dgt(23℃ ± 5 ℃, por debajo del 80% de humedad relativa)
Rango de detección 0.1mA ~ 100.0mA
Transmission mode wireless RF mode
Transmission frequency 433megahercio
Transmission distance ≥40mm
Temperatura de trabajo -30℃ ~ 70 ℃
Fuente de alimentación 3 No. 7 alkaline dry batteries.
Peso 0.45kg
Volumen 180×100×35mm

cable grounding fault locator

Signal receiver

Receive and display data from a handheld data detector.
You can lock and hold data.
In automatic pairing, the communication status with the pliers meter is displayed automatically.
Automatic display device voltage, automatic low voltage alarm.
Display the detected signal size in digital mode.
Data transmitted by handheld signal detection devices can be stored.
Modo de visualización Large screen LCD, backlight function.
Historical data can be stored ≥500 times.
You can set up a variety of ways to work.
Data from the host and receiver can be read.
Temperatura de trabajo -30℃ ~ 70 ℃.
Fuente de alimentación 5 No. 5 alkaline dry batteries.
Peso 0.45kg
Volumen 205 ×100×35mm