Beskrywing

KGZW-OL Battery Online Monitoring System

Produk Inleiding
KGZW-OL battery online monitoring system is mainly used for railway traction substation, communication room and UPS power battery status monitoring and analysis, is based on the battery internal resistance, terminal voltage as the main monitoring parameters, the battery performance status monitoring system. Found that the performance of serious deterioration fault battery immediately alarm; Track the performance balance of the battery to provide a basis for “fine” battery maintenance.

 

KGZW-OL Battery Online Monitoring System

Produk Eienskappe
1. Unique internal resistance test technology to avoid battery damage and system impact during the test.
2, online discharge, by measuring the battery voltage, stroom, calculate the discharge capacity, according to the set discharge requirements, automatically prompt the user to end the discharge.
3, with network alarm, SMS alarm and sound and light alarm function.
4, can be 4, 8, 24, 32, 48, 54, 108, 256 road expansion.
5, automatic inspection battery internal resistance, terminal voltage, automatic recording of monitoring data.
6, controlled single inspection, inspection battery internal resistance, terminal voltage, automatic recording of test data.
7, automatic monitoring of battery performance balance, diagnosis of battery failure, when the battery failure can automatically alarm.
8, automatically analyze the internal resistance trend, predict the battery life.
9, single battery and battery pack performance status can be observed in the field, can also be observed in the data center. The logo is clear and the display is intuitive.
10, on-site detection does not need manual intervention, avoiding the risk of short circuit and electric shock caused by manual detection error.
11, fully isolated independent test circuit, neither interference by user equipment, nor affect the normal operation of user equipment and battery pack.
12, battery resource management comprehensive digital, inligting.
13, full use of battery resources, save funds, benefit environmental protection.

 

KGZW-OL Battery Online Monitoring System

Produk funksie
Through GPRS or Ethernet remote monitoring, the application of powerful and perfect PC system management software, you can manage the battery in real time through the following functions:
1, timing internal resistance detection function
The system can set automatic timing detection of battery internal resistance, the minimum setting is once every 10 minute. Op dieselfde tyd, the internal resistance of the whole battery or a single battery can be detected on the server. The battery voltage value can also be measured at the same time as the internal resistance is tested.
2, voltage inspection function
The system inspects parameters such as battery pack voltage, stroom, positive and negative electrode temperature, and battery voltage. The inspection interval can be set. The minimum interval is 20 sekondes.
3, capacity monitoring function
When the battery pack is being discharged or charged, the battery monitor automatically performs a capacity test. The discharge capacity and charging capacity of each battery and battery pack can be tested. Op dieselfde tyd, the charging and discharging process is observed remotely. It can cooperate with the annual nuclear outburst discharge, and the whole process of monitoring the battery pack voltage and discharge current and the voltage change of each battery during discharge.
4. Alarm recording function
Upper and lower limits can be set for battery pack voltage, enkel battery spanning, battery internal resistance, temperatuur, ens. When the monitor detects that a parameter exceeds the set upper and lower limits, the monitor can alarm through sound and light, and record the event. The user can find the abnormal working status of the battery string.
5, battery quality analysis and report analysis function
B/S structure database management for long-term tracking and monitoring of the battery’s internal resistance and voltage, and can form monthly, quarterly, annual monitoring reports, a comprehensive grasp of battery operation and maintenance status.

 

KGZW-OL Battery Online Monitoring System

Produk Parameters
Item Parameter
kommunikasie RS232/RS485/Ethernet/USB
Single section voltage 2V 0-3V accuracy 0.5%rdg±6rdgt
12V0-16Vaccuracy0.2﹪rdg±6rdgt
Internal resistance range and accuracy 2V0.00-10.0mΩ 12V0.00-100.0mΩ accuracy 0.2﹪rdg±6rdgt
Global voltage range 0-300V(Larger voltage can be customized)
Global current range 0-100A(Optional current sensor)
Number of connections 4、8、12、24、32、48、54、108、256路
depositor 128MFlash
Skerm 128×64 LCD screen
grootte 420×390×142mm(wall-mounted) 483×386×185mm(Rack Scale Architecture)
gewig 5Kg